Smart-UPS 700のバッテリーが切れた・・・再び

この記事は2年以上前に書いたものです。
そのため情報が古い可能性があります。ご了承ください。m(_ _)m

からアラーム音が鳴り、要バッテリ交換LEDが赤く点灯していた。
(Smart-UPSの警告音(アラーム音)の種類Smart-UPSの前面パネルのLED概要)

また、apcupsdから次のようなメールがちょくちょく来てた。

Subject: qos UPS battery needs changing NOW.
 
qos UPS battery needs changing NOW.
 
APC      : 001,053,1336
DATE     : 2010-11-06 19:19:08 +0900  
HOSTNAME : qos
VERSION  : 3.14.8 (16 January 2010) debian
UPSNAME  : UPS_IDEN
CABLE    : Custom Cable Smart
MODEL    : SMART-UPS 700
UPSMODE  : Stand Alone
STARTTIME: 2010-09-10 02:41:15 +0900  
STATUS   : ONLINE REPLACEBATT
LINEV    : 100.7 Volts
LOADPCT  :  58.7 Percent Load Capacity
BCHARGE  : 099.0 Percent
TIMELEFT :  18.0 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME  : 0 Seconds
MAXLINEV : 101.4 Volts
MINLINEV : 099.4 Volts
OUTPUTV  : 100.7 Volts
SENSE    : High
DWAKE    : 000 Seconds
DSHUTD   : 180 Seconds
DLOWBATT : 05 Minutes
LOTRANS  : 090.0 Volts
HITRANS  : 110.0 Volts
RETPCT   : 000.0 Percent
ITEMP    : 49.0 C Internal
ALARMDEL : 5 seconds
BATTV    : 27.2 Volts
LINEFREQ : 50.0 Hz
LASTXFER : Automatic or explicit self test
NUMXFERS : 2
XONBATT  : 2010-11-03 19:59:30 +0900  
TONBATT  : 0 seconds
CUMONBATT: 5 seconds
XOFFBATT : 2010-11-03 19:59:35 +0900  
LASTSTEST: 2010-11-03 19:59:30 +0900  
SELFTEST : NO
STESTI   : 336
STATFLAG : 0x07000088 Status Flag
DIPSW    : 0x00 Dip Switch
REG1     : 0x00 Register 1
REG2     : 0x00 Register 2
REG3     : 0x00 Register 3
MANDATE  : 12/19/01
SERIALNO : XXXXXXXXXXXX
BATTDATE : 12/19/01
NOMOUTV  : 100 Volts
NOMBATTV :  24.0 Volts
EXTBATTS : 0
FIRMWARE : 50.14S.A
APCMODEL : GWA
END APC  : 2010-11-06 19:19:10 +0900

Smart-UPS 700のバッテリーが切れた」で、バッテリーをPXL12072に変更してから1年と11ヶ月くらいしか経ってないのに。。
アラームがうるさかったので、また互換バッテリーを購入することに。今度は、完全密封型鉛蓄電池(12V8Ah)WP8-12を、\2,450 X 2 + \500(送料) + \300(代引き手数料) = \5,700 で。

注文してから2日後に届く。
WP8-12_001 WP8-12_002 WP8-12_003 WP8-12_004 WP8-12_005 WP8-12_007

Smart- 700 は赤ランプ点灯中。
WP8-12_008

フロントパネルを外す。
WP8-12_009 WP8-12_010

バッテリーの下に挟まってる紙は、バッテリーを取り出しやすくするため。
どこかのサイトに書いてたってそれを真似した。
WP8-12_011

PXL12072。
WP8-12_012 WP8-12_014

WP8-12に、両面テープを貼って、ケーブルを接続。
WP8-12_016 WP8-12_017

バッテリーが入っていない状態のSmart-UPS 700
WP8-12_018 WP8-12_019 WP8-12_022 WP8-12_023

WP8-12を取り付ける。
WP8-12_024

TESTボタンを長押ししてセルフテストを動作させると・・・。
要バッテリー交換LEDが消えた!!
WP8-12_026

フロントパネルを取り付ける。
WP8-12_027 WP8-12_028

バッテリー交換した日付を更新。
前回忘れてたけど、今回は「jlb APC SU700J のバッテリィ交換」を参考に実施。

% sudo apctest

2010-11-11 01:36:41 apctest 3.14.8 (16 January 2010) debian
Checking configuration ...
Attached to driver: apcsmart
sharenet.type = DISABLE
cable.type = CUSTOM_SMART

You are using a SMART cable type, so I'm entering SMART test mode
mode.type = APCSMART_UPS
Setting up the port ...
apctest FATAL ERROR in device.c at line 71
Unable to create UPS lock file.
  If apcupsd or apctest is already running,
  please stop it and run this program again.
apctest error termination completed

早速apcupsdを止めろと怒られる。

% sudo /etc/init.d/apcupsd stop
Stopping UPS power management: apcupsd.
% sudo apctest


2010-11-11 01:37:22 apctest 3.14.8 (16 January 2010) debian
Checking configuration ...
Attached to driver: apcsmart
sharenet.type = DISABLE
cable.type = CUSTOM_SMART

You are using a SMART cable type, so I'm entering SMART test mode
mode.type = APCSMART_UPS
Setting up the port ...
Hello, this is the apcupsd Cable Test program.
This part of apctest is for testing Smart UPSes.
Please select the function you want to perform.

1) Query the UPS for all known values
2) Perform a Battery Runtime Calibration
3) Abort Battery Calibration
4) Monitor Battery Calibration progress
5) Program EEPROM
6) Enter TTY mode communicating with UPS
Q) Quit

Select function number: 5

This is the EEPROM programming section of apctest.
Please select the function you want to perform.

 1) Print EEPROM values
 2) Change Battery date
 3) Change UPS name
 4) Change sensitivity
 5) Change alarm delay
 6) Change low battery warning delay
 7) Change wakeup delay
 8) Change shutdown delay
 9) Change low transfer voltage
10) Change high transfer voltage
11) Change battery return threshold percent
12) Change output voltage when on batteries
13) Change the self test interval
14) Set EEPROM with conf file values
 Q) Quit

Select function number: 2

Enter new battery date -- DD/MM/YY: 11/11/10

Attempting to update UPS battery date ...
The old UPS battery date is: 12/19/01
The new UPS battery date is: 11/11/10

 1) Print EEPROM values
 2) Change Battery date
 3) Change UPS name
 4) Change sensitivity
 5) Change alarm delay
 6) Change low battery warning delay
 7) Change wakeup delay
 8) Change shutdown delay
 9) Change low transfer voltage
10) Change high transfer voltage
11) Change battery return threshold percent
12) Change output voltage when on batteries
13) Change the self test interval
14) Set EEPROM with conf file values
 Q) Quit

Select function number: Q

2010-11-11 01:38:31 End EEPROM programming.

1) Query the UPS for all known values
2) Perform a Battery Runtime Calibration
3) Abort Battery Calibration
4) Monitor Battery Calibration progress
5) Program EEPROM
6) Enter TTY mode communicating with UPS
Q) Quit

Select function number: Q

2010-11-11 01:38:34 End apctest.
% sudo /etc/init.d/apcupsd start
Starting UPS power management: apcupsd.

Smart-UPS 700から情報取得。

% sudo apcaccess status
APC      : 001,051,1222
DATE     : 2010-11-11 01:57:30 +0900
HOSTNAME : qos
VERSION  : 3.14.8 (16 January 2010) debian
UPSNAME  : UPS_IDEN
CABLE    : Custom Cable Smart
MODEL    : SMART-UPS 700
UPSMODE  : Stand Alone
STARTTIME: 2010-11-11 01:38:43 +0900
STATUS   : ONLINE
LINEV    : 100.7 Volts
LOADPCT  :  57.2 Percent Load Capacity
BCHARGE  : 099.0 Percent
TIMELEFT :  18.0 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME  : 0 Seconds
MAXLINEV : 101.4 Volts
MINLINEV : 099.4 Volts
OUTPUTV  : 101.4 Volts
SENSE    : High
DWAKE    : 000 Seconds
DSHUTD   : 180 Seconds
DLOWBATT : 05 Minutes
LOTRANS  : 090.0 Volts
HITRANS  : 110.0 Volts
RETPCT   : 000.0 Percent
ITEMP    : 46.8 C Internal
ALARMDEL : 5 seconds
BATTV    : 27.2 Volts
LINEFREQ : 50.0 Hz
LASTXFER : Automatic or explicit self test
NUMXFERS : 0
TONBATT  : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STESTI   : 336
STATFLAG : 0x07000008 Status Flag
DIPSW    : 0x00 Dip Switch
REG1     : 0x00 Register 1
REG2     : 0x00 Register 2
REG3     : 0x00 Register 3
MANDATE  : 12/19/01
SERIALNO : XXXXXXXXXXXX
BATTDATE : 11/11/10
NOMOUTV  : 100 Volts
NOMBATTV :  24.0 Volts
EXTBATTS : 0
FIRMWARE : 50.14S.A
APCMODEL : GWA
END APC  : 2010-11-11 01:58:07 +0900

BATTDATEが更新されてる。
それにしても、ITEMPが高ぇ。。常夏か?